Figure 1. Input of switchmode might supplies without PFC. The voltage waveform is a sinewave in addition to the electrical flow waveform is a pulse or spike. PF<1 span="">
1>
1>
The Power Factor tin hold upwards improved yesteryear using PFC circuits. These circuits “smooth out” the pulsating air conditioning current, improving the PF, in addition to reducing the chances of a circuit breaker tripping prematurely. There are ii basic types of PFC, passive in addition to active. Passive PFC circuits are less expensive in addition to typically tin right the PF to nigh 0.85. Active PFC circuits are the most popular, are built into the switchmode might render in addition to tin increment the PF to 0.98 or higher. The closer the PF comes to beingness 1.0, the improve the functioning of the might supply. Ideally, nosotros desire to halt upwards alongside the input voltage in addition to electrical flow waveforms beingness sinusoidal in addition to inward stage alongside each other every bit shown inward Fig. 2.
PFC is Required yesteryear International Regulations
An of import argue to accept PFC inward your might render is to comply alongside international regulations, specially if y'all intend to sell your equipment inward Europe. Since 2001, the European Union (EU) established limits on harmonic currents that tin look on the mains (AC line) of switchmode might supplies. Today, the most of import rule is the “European Norm” EN61000-3-2. This rule applies to might supplies alongside input might of 75 watts or greater, in addition to that trace upwards to sixteen amps off the mains. It sets severe limits on the harmonic currents upwards to the 39th, when measured at the input of switchmode might supplies.
For example, the offset harmonic is the primary input frequency, typically l Hz for the European Union countries. The 3rd harmonic is 150 Hz, in addition to the 39th harmonic is 1,950 Hz. These unwanted harmonic currents accept a straight human relationship to the Power Factor of switchmode might supplies. Therefore, might supplies that encounter EN61000-3-2 inherently accept high might factors that are typically 0.97 or higher.
PFC Increases the Supply’s Output Power Capability
The PF, much similar the supply’s efficiency rating, determines the amount of useful might a switchmode might render tin describe from the air conditioning work in addition to and then deliver to its output load. Specifically, the formula that determines this is:
VLrms x ILrms x PF x Eff = Pout
As an example, if a might render is operating off of 120VAC line, which is protected yesteryear 15A circuit breaker, UL guidelines state y'all should non describe to a greater extent than than 12A. So, using the formula above, nosotros tin compare ii might render examples alongside dissimilar Power Factors, every bit follows:
Example A: No PFC, PF = 0.65, 85% Efficiency, 120VAC input, 12A max. current:
Therefore: 120VAC x 12A x 0.65 x 0.85 = 796 Watts Output Power
Example B: PFC used, PF=0.98, 85% Efficiency, 120VAC input, 12A max. current:
Therefore: 120VAC x 12A x 0.98 x 0.85 = 1200 Watts Output Power
As tin hold upwards seen above, the might render inward Example B (with PFC) tin deliver 404 Watts or 51% to a greater extent than might to its output charge than the non-PFC supply, a pregnant increase.
Why produce I necessitate PFC?
Influenza A virus subtype H5N1 might render alongside PFC tin render higher output charge currents than those without PFC. PFC significantly reduces the air conditioning electrical flow harmonics, leaving mainly the “fundamental” electrical flow frequency that is in-phase alongside the voltage waveform (Fig. 2). International regulations dictate the substantial reduction of harmonic currents. The vast bulk of AC-DC might supplies manufactured yesteryear Lambda Americas has active PFC, is inward accordance alongside EN61000-3-2 in addition to provides typical might factors inward the make of 0.97 to 0.99.